Pipe velocity check and heat-carrying capacity

A=π(d/1000)24v=Vl60000Ar=vvl×100Pmax=vlA×1000cpΔT
where
A
pipe bore area (m²)
d
pipe internal diameter (mm)
v
water velocity (m/s)
Vl
volume flow rate (litres/min)
r
velocity as % of limit
vl
design velocity limit (m/s)
Pmax
heat carried at the velocity limit (kW)
cp
specific heat capacity of water (kJ/kg·K)
ΔT
flow minus return temperature (K)
Explain this equation

Checks the water speed in a pipe for a given flow, and shows how much heat that pipe can carry at your velocity limit. Use it to pick primary pipe sizes for a heat pump.

A is the bore area with the diameter converted to metres. The flow in litres per minute is divided by 60,000 to give cubic metres per second (60 seconds, 1000 litres per m³); dividing by area gives speed. At the velocity limit the pipe passes v_l × A cubic metres per second; times 1000 gives kilograms per second, and times c_p ΔT gives kW.

Velocity is flow over area; heat capacity follows from the flow-rate equation at the maximum allowed flow.

Sense check: 23 litres a minute in 22 mm copper (20.2 mm bore) runs at about 1.2 m/s, over a 1 m/s limit. At 1 m/s and 5 K that pipe carries about 6.7 kW.

Watch out: too fast is noisy and wastes pump energy; too slow is fine for heat but larger pipe costs more. Use the true internal diameter.

Checks the water speed in a pipe at the design flow rate, and shows how much heat that pipe can carry at your velocity limit.

litres/min
m/s
K
kJ/kg·K

Enter your values to see the result.

Good to know

Internal diameters of BS EN 1057 Table X (R250) copper: 15 × 0.7 mm → 13.6 mm, 22 × 0.9 mm → 20.2 mm, 28 × 0.9 mm → 26.2 mm. For plastic pipe use the maker’s bore, and remember insert fittings narrow it further. Typical design limits are 0.5–1.5 m/s; around 1 m/s keeps noise and pressure drop reasonable in domestic copper. Water content per metre is about 0.15 l (15 mm), 0.32 l (22 mm) and 0.54 l (28 mm).

Common mistake

Using the outside diameter. A 22 mm tube has a 20.2 mm bore, which gives about 19% more velocity than 22 mm would suggest.

Limits

Average velocity in straight pipe. It does not give pressure drop: use the pipe sizing tables in CIBSE DHDG or the manufacturer’s data with the circulator curve.