Tradefox Reference
Crimp terminal and ferrule colour codes. And every lug die code.
Crimp terminals, bootlace ferrules and cable lugs are colour-coded and numbered by size, but the codes change between countries and makers. This page sets out the red, blue and yellow terminal convention, Japan’s JIS sizes, the DIN, French and German ferrule codes, DIN 46235 die codes, North America’s Color-Keyed lugs, and the Australian and Chinese standards, side by side.
Colour and size codes. Pick a system.
Each system shows its terminals drawn out, the standard or convention behind it and the sources we checked. On-screen colours are approximate, and drawings are not to scale.
Pre-insulated terminals Worldwide trade convention
Red, blue and yellow ring, fork, pin, blade and butt connectors
- Set by
- Industry convention followed by most makers. It is not fixed in one international standard.
- Used in
- UK, Europe, North America, Australia, Asia and most other markets
- Sizes
- Given in mm² and AWG on the pack and usually on the sleeve
- Sleeves
- PVC (vinyl), nylon or heat-shrink. Nylon and heat-shrink usually take higher temperatures: check the rating
The sleeve colour tells you which conductor range the barrel takes. The ranges overlap slightly at the edges and each maker publishes its own exact limits, so read the pack before you rely on the colour alone.
- Two sizes share yellow. The small mini yellow (0.2 to 0.5 mm²) and the large yellow (4 to 6 mm²) look alike on a shelf, so check the barrel size.
- Maker limits differ at the edges: some quote red up to 1.6 mm², blue 1.0 to 2.6 mm² and yellow 2.5 or 2.7 to 6.6 mm².
- US makers often rate red as 22 to 18 AWG rather than 22 to 16 AWG. Use the AWG range printed on the pack.
- Insulated terminals are also made above 6 mm² (10 AWG), for example 8 AWG red and 4 AWG yellow nylon types. For conductors larger than 10 AWG (6 mm²), colours are set by each maker, so the red, blue and yellow ranges no longer apply.
- Use the ratchet tool and die made for insulated terminals, matched by colour. Plain pliers or a bare-terminal die split the sleeve.
- Many insulated terminals also grip the cable insulation behind the barrel. Check both the conductor crimp and the insulation-support crimp.
Sources (6) Corroborated
- Hilltop Products: pre-insulated crimp terminals (opens in a new tab)Red 0.5 to 1.5 mm² (22 to 16 AWG), blue 1.5 to 2.5 mm² (16 to 14 AWG), yellow 4 to 6 mm² (12 to 10 AWG).
- RS PRO insulated pin terminals: colour code (opens in a new tab)Mini yellow 0.2 to 0.5, red 0.5 to 1.5, blue 1.5 to 2.5, yellow 2.5 to 6.5 mm².
- TE Connectivity PLASTI-GRIP spade terminals (RS listing) (opens in a new tab)Maker ranges: red 0.25 to 1.6, blue 1.0 to 2.6, yellow 2.7 to 6.6 mm².
- Panduit PNR insulated ring terminals (opens in a new tab)US maker ranges: red 22 to 18 AWG, blue 16 to 14 (some 18 to 14) AWG, yellow 12 to 10 AWG.
- NSI nylon-insulated ring terminal, 8 AWG red (Gexpro) (opens in a new tab)Insulated terminals are made above 10 AWG; this maker colours 8 AWG red.
- Kent ring tongue terminal, 4 AWG yellow (opens in a new tab)Example of a large insulated terminal: 4 AWG, yellow.
JIS C 2805 Japan
Crimp-type terminal lugs for copper conductors
- Issued by
- Japanese Industrial Standards Committee
- Size names
- Nominal mm²: 1.25, 2, 3.5, 5.5, 8, 14, 22, 38 and up to 325; makers sell a smallest size as 0.3 or 0.5
- Shapes
- R type (ring) is the common bolted terminal; Y type (fork) is also made
- Colours
- Set by makers, not by JIS C 2805: the standard covers the terminal itself
Japanese terminals are named by nominal size, so an R 2-4 is a ring for 2 mm² nominal wire on an M4 screw. Insulated versions from Japanese makers use the same red, blue and yellow idea as the rest of the world, tied to the JIS sizes.
- The wire ranges come from the AWG conversions the makers print: 1.25 covers 22 to 16 AWG, 2 covers 16 to 14 AWG and 5.5 covers 12 to 10 AWG.
- Clear (uncoloured) insulation is also sold in every size, so a clear sleeve tells you nothing about its range.
- Many JIS terminals are also UL listed, but the size names are Japanese: an 8, 14 or 22 is a nominal mm² size, not an AWG gauge.
Sources (3) Corroborated
- JST solderless terminals, R type (JIS C 2805) (opens in a new tab)JIS-marked ring terminals: yellow 26 to 22 AWG, red 22 to 16 AWG, blue 16 to 14 AWG, yellow 12 to 10 AWG.
- Nichifu R type insulated terminals (MISUMI) (opens in a new tab)Standard colours: 1.25 mm² red, 2 mm² blue, 5.5 mm² yellow.
- MISUMI: R type bare terminals to JIS C 2805 (opens in a new tab)Conforms to JIS C 2805 (crimp-type terminal lugs for copper conductors) and UL 486A; sizes 0.3 to 325 mm².
DIN 46228-4 Germany, Europe and widely exported
Insulated bootlace (wire end) ferrules: dimensions and collar colours
- Issued by
- DIN (German Institute for Standardization)
- Parts
- Part 1 covers bare ferrules; Part 4 covers ferrules with a plastic collar
- Range
- 0.5 to 50 mm² in the standard; makers add 0.14, 0.25 and 0.34 mm² outside it
- North America
- UL 486F covers ferrules but sets no colour code; Phoenix Contact’s table gives the same colours for UL 486F (Form E) as for DIN 46228-4. Under UL 486F a ferrule’s plastic collar is for identification only, not insulation
A ferrule gathers the strands of a flexible conductor into a solid pin so that a screw or spring terminal clamps every strand. The DIN code repeats a short colour cycle, so the same colour turns up at several sizes.
- Colours repeat: grey is 0.75 and 4 mm², red is 1, 10 and 35 mm², blue is 2.5, 16 and 50 mm², yellow is 6 and 25 mm². Read the size on the strip or box.
- The small sizes 0.14 (grey), 0.25 (yellow) and 0.34 mm² (turquoise) are maker additions, not part of DIN 46228-4.
- Twin ferrules take two conductors in one pin. In the DIN colours, 2 x 0.5 is white, 2 x 0.75 grey, 2 x 1 red and 2 x 1.5 black. Use a twin ferrule rather than forcing two wires into a single one.
Sources (6) Corroborated
- Phoenix Contact: ferrule colour code tables (opens in a new tab)Side-by-side ferrule colours for DIN 46228-4, NF C 63-023 and the special (German) colour code, 0.14 to 50 mm².
- Phoenix Contact: ferrule colour codes (AWG and mm²) (opens in a new tab)Same three codes listed against AWG sizes, including 25, 35 and 50 mm².
- Bossard: DIN colour-code ferrule assortment (opens in a new tab)DIN colours 0.5 white, 0.75 grey, 1 red, 1.5 black, 2.5 blue, 4 grey, 6 yellow, 10 red, 16 blue.
- Lapp: DIN 46228-4 ferrules on coil (opens in a new tab)Manufacturer data sheet: 0.5 white to 2.5 blue in the DIN code.
- Rapid: DIN twin ferrule assortment (opens in a new tab)DIN colour twin ferrules: 2 x 0.5 white, 2 x 0.75 grey, 2 x 1 red, 2 x 1.5 black.
- UL 486F scope: bare and covered ferrules (opens in a new tab)Third edition, December 2024; ferrules from 26 AWG (0.14 mm²) to 750 kcmil (380 mm²).
NF C 63-023 France, UK trade stock, Australia and others
Ferrule colour code used by French makers and much UK and Australian stock
- Issued by
- AFNOR (France)
- Where you see it
- Legrand Starfix and many UK and Australian bootlace ranges
- Range
- About 0.25 to 50 mm²
The French code gives each common size its own colour up to 10 mm², which many electricians find easier than the DIN cycle. It shares white (0.5), red (1) and black (1.5) with DIN but differs at 0.75 and from 2.5 mm² up.
- The biggest trap is 2.5 mm²: grey in the French code, blue in DIN. And 0.75 mm² is blue in the French code but grey in DIN.
- 16 mm² is listed as ivory by some makers and white by others; the smallest sizes also vary (Legrand lists 0.25 turquoise and 0.34 green).
- Twin ferrules in the French code: 2 x 0.75 blue, 2 x 1 red, 2 x 1.5 black, 2 x 2.5 grey.
- If a panel mixes French and DIN stock, the colours no longer mean one size. Keep one code per job.
Sources (4) Corroborated
- Phoenix Contact: ferrule colour code tables (opens in a new tab)Side-by-side ferrule colours for DIN 46228-4, NF C 63-023 and the special (German) colour code, 0.14 to 50 mm².
- Legrand Starfix ferrules (NF C 63-023) (opens in a new tab)French-code colours from 0.25 to 50 mm², singles and doubles, conforming to NF C 63-023.
- Rapid / TruConnect: French and German type ferrules (opens in a new tab)Supplier table giving French type (0.5 white to 6 green) and German type (0.25 light blue to 4 grey).
- Voltex: bootlace crimps, German and French colours (opens in a new tab)Australian supplier table, 0.5 to 25 mm², German and French colour codes side by side.
Special (German) colour code Germany and makers worldwide
Widely sold alternative to the DIN cycle, not a DIN standard
- Also called
- “German colour code”, “colour code 2” or “special colour code”
- Set by
- Maker convention. It is not DIN 46228-4.
- Range
- About 0.14 to 50 mm²
This code gives every size up to 50 mm² its own colour. Phoenix Contact, Weidmüller and many others sell it alongside DIN and French ranges, so the same size can arrive in three different colours.
- Despite the name it is not the DIN code. A white ferrule is 0.75 mm² here but 0.5 mm² in DIN and French stock.
- Small sizes in this code are usually 0.14 grey, 0.25 light blue and 0.34 turquoise.
- Some catalogues call this the “DIN colour code 2”. Check which table a box refers to before mixing stock.
Sources (4) Corroborated
- Phoenix Contact: ferrule colour code tables (opens in a new tab)Side-by-side ferrule colours for DIN 46228-4, NF C 63-023 and the special (German) colour code, 0.14 to 50 mm².
- Phoenix Contact: ferrule colour codes (AWG and mm²) (opens in a new tab)Same three codes listed against AWG sizes, including 25, 35 and 50 mm².
- Voltex: bootlace crimps, German and French colours (opens in a new tab)Australian supplier table, 0.5 to 25 mm², German and French colour codes side by side.
- Rapid / TruConnect: French and German type ferrules (opens in a new tab)Supplier table giving French type (0.5 white to 6 green) and German type (0.25 light blue to 4 grey).
DIN 46235 Germany, Europe and IEC markets
Compression cable lugs for copper conductors: dimensions, marking and die codes
- Issued by
- DIN (German Institute for Standardization)
- Crimp
- Hexagonal dies to DIN 48083 Part 4 are recommended
- Performance tests
- IEC 61238-1 series (EN IEC 61238-1-1 up to 1 kV)
Every DIN 46235 lug is stamped with a die code. Fit the die with the same number, crimp, and the die prints its number back onto the barrel so an inspector can check it afterwards. A marking such as KL 22 12-150 means maker KL, die code 22, M12 bolt, 150 mm².
- Die codes belong to DIN 46235 lugs only. Standard (non-DIN) tube lugs have different tube sizes and are crimped to the lug maker’s own chart.
- DIN compression lugs are longer than standard tube lugs and need more crimps; the number and width of crimps is marked or given by the maker.
- Aluminium lugs use their own codes (DIN 46329 tube sizes): never use the copper code for an aluminium lug.
Sources (7) Corroborated
- Hilpress: compression cable lugs DIN 46235 (opens in a new tab)DIN 46235 sets dimensions for all makers; hexagonal inserts recommended; die code left on the lug.
- Klauke crimping die HD 4 (opens in a new tab)DIN 46235, 6 mm²: code 5.
- Klauke crimping die HD 13 (DIN 46235) (opens in a new tab)Die codes: 10 mm² 6, 16 mm² 8, 25 mm² 10, 35 mm² 12, 50 mm² 14, 70 mm² 16.
- Klauke die chart (catalogue extract) (opens in a new tab)DIN 46235 codes 70 to 185 mm²: 16, 18, 20, 22, 25.
- Klauke crimping die HD 25 (DIN 46235) (opens in a new tab)Die codes: 150 mm² 22, 185 mm² 25, 240 mm² 28, 300 mm² 32, 400 mm² 38, 500 mm² 42.
- Thorne & Derrick: DIN 46235 lug marking (opens in a new tab)Marking example KL 22 12-150: maker, die code, M12 bolt, 150 mm².
- Thorne & Derrick: DIN 48083 hexagonal dies (opens in a new tab)DIN 46235 lugs are crimped with hexagonal dies to DIN 48083 Part 4.
UL 486A-486B and Color-Keyed USA, Canada and Mexico
Wire connectors standard, with the Color-Keyed die system used on compression lugs
- Standard
- UL 486A-486B, harmonised with CSA C22.2 No. 65 and NMX-J-543-ANCE
- Sizes
- AWG and kcmil; metric ratings may be added but AWG/kcmil ratings are mandatory
- Ferrules
- UL 486F covers bare and covered ferrules
Copper compression lugs in North America carry a coloured band and a die number. The matching die is painted the same colour and embosses the same number, so a red 21 lug takes a red 21 die. Color-Keyed is a Thomas & Betts (now ABB) system; Panduit and other makers use the same colours on their dies.
- Colours and numbers here are for copper code-conductor lugs. Connectors for aluminium conductors use other colours, for example gold, tan, olive and ruby, so never assume a colour means the same size on an aluminium part.
- Two-hole lugs for equipment pads are drilled to NEMA spacing: 1/2 in bolts on 1-3/4 in centres for the common large pattern.
- Long-barrel and short-barrel lugs of the same size can need a different number of crimps. Follow the chart for the lug and tool.
Sources (7) Corroborated
- UL 486A-486B scope (GlobalSpec) (opens in a new tab)Harmonised wire connector standard; copper 30 AWG to 2000 kcmil; metric ratings optional alongside AWG/kcmil.
- CSA C22.2 No. 65 (tri-national with UL 486A-486B) (opens in a new tab)Harmonised ANCE, CSA and UL standard for wire connectors.
- ABB / Thomas & Betts Color-Keyed lug chart (opens in a new tab)Die colour and die code by wire size: 8 AWG red 21, 6 AWG blue 24, 4 AWG grey 29, 2 AWG brown 33, 1/0 pink 42, 2/0 black 45, 4/0 purple 54, 250 kcmil yellow 62.
- Thomas & Betts installing dies (Canada) (opens in a new tab)Color-Keyed die table 8 AWG to 250 kcmil, including 1 AWG green 37 and 3/0 orange 50.
- Panduit CD-2001 die selection (opens in a new tab)Same colours on another maker's dies: 4/0 purple P54, 250 kcmil yellow P62, 300 kcmil white P66.
- BURNDY NEMA-spaced board lugs (opens in a new tab)NEMA standard spacing: 1/2 in stud holes spaced 1-3/4 in apart.
- UL 486F scope: bare and covered ferrules (opens in a new tab)Third edition, December 2024; ferrules from 26 AWG (0.14 mm²) to 750 kcmil (380 mm²).
AS/NZS 4325.1 Australia and New Zealand
Compression and mechanical connectors for power cables
- Issued by
- Standards Australia and Standards New Zealand
- Type
- A test standard reproduced from IEC 1238-1:1993 (now IEC 61238-1), for copper from 10 mm² and aluminium from 16 mm². It does not set lug dimensions. Listed as withdrawn in Australia in 2025: check its current status
- Lug styles
- Standard copper lugs and bell-mouth lugs for flexible cable
- Tooling
- Some local makers, such as CABAC, make lugs to Australian dimensions for Australian dies
Local lug ranges are often made to suit local tooling, so an imported DIN or North American lug may not match the die in an Australian crimper. Always use the die the lug maker specifies. Bell-mouth lugs, with a flared entry, are the usual choice for fine-stranded flexible cable.
- Pre-insulated terminals follow the worldwide red, blue and yellow convention.
- Bootlace ferrules are sold in both French and German colour codes, so check the table on the box.
- Large flexible cables may not fit the nominal lug. Makers advise a bell-mouth lug or their own oversize method rather than trimming strands.
Sources (5) Corroborated
- AS/NZS 4325.1:1995 listing (standards.ie) (opens in a new tab)Test methods and requirements, reproduced from IEC 1238-1:1993; copper from 10 mm², aluminium from 16 mm²; listed as withdrawn in Australia (2025).
- HellermannTyton Australia: lugs and links (opens in a new tab)Lugs made to AS/NZS 4325 Part 1.
- ABB Spec-Kon cable termination solutions (opens in a new tab)AS/NZS 4325-1 and IEC 61238 conformant lugs; bell-mouth lugs for flexible cable.
- CABAC copper crimp lugs data sheet (CEF) (opens in a new tab)Lugs made to Australian dimensions for standard Australian tooling, AS/NZS 4325 Part 1.
- Voltex: bootlace crimps, German and French colours (opens in a new tab)Australian supplier table, 0.5 to 25 mm², German and French colour codes side by side.
GB/T 14315-2008 China
Compression copper, aluminium and copper-aluminium lugs and ferrules for power cables
- Issued by
- Standardization Administration of China
- Scope
- Power cable conductors up to 35 kV (Um = 40.5 kV); copper 10 to 630 mm², aluminium 16 to 630 mm²
- Trade names
- DT copper lugs, DL aluminium lugs, DTL copper-aluminium lugs
Chinese tube lugs are commonly sold by type letter and size, for example DT-95 for a 95 mm² copper lug. The barrels differ from DIN 46235 lugs, so use the die set recommended for that lug.
- GB/T 14315-2008 replaced the 1993 edition. The “ferrules” in its title are joint sleeves (connecting tubes), not bootlace ferrules.
- DTL lugs join aluminium cable to copper busbars or studs. Do not use a DT copper lug on aluminium conductors.
- We could not confirm a national colour code for Chinese lugs from the sources checked.
Sources (2) Check local rules
- GB/T 14315-2008 summary (Code of China) (opens in a new tab)Compression copper, aluminium and Cu-Al transition lugs and ferrules for power cables up to 35 kV.
- Chalco: DL, DT and DTL lugs to GB/T 14315 (opens in a new tab)DT is copper, DL aluminium, DTL copper-aluminium; DT sizes 16 to 240 mm².
Side by side. Same size, different colour.
What each system shows for each conductor size. Select a column heading to open its details. “Maker colours” means the red, blue and yellow ranges stop at about 6 mm²: larger insulated terminals exist, but each maker sets its own colours.
| Size | |||||
|---|---|---|---|---|---|
| 0.5 mm² | Red | White | White | Orange | — |
| 0.75 mm² | Red | Grey | Blue | White | — |
| 1 mm² | Red | Red | Red | Yellow | — |
| 1.5 mm² | Red or blue (edge of both) | Black | Black | Red | — |
| 2.5 mm² | Blue | Blue | Grey | Blue | — |
| 4 mm² | Yellow | Grey | Orange | Grey | — |
| 6 mm² | Yellow | Yellow | Green | Black | 5 |
| 10 mm² | Maker colours | Red | Brown | Ivory | 6 |
| 16 mm² | Maker colours | Blue | Ivory | Green | 8 |
| 25 mm² | Maker colours | Yellow | Black | Brown | 10 |
| 35 mm² | Maker colours | Red | Red | Beige | 12 |
| 50 mm² | Maker colours | Blue | Blue | Olive | 14 |
mm² and AWG. Close is not the same.
Terminals and lugs are rated in metric sizes (mm²) or in AWG and kcmil. The two series do not line up, so a lug for the nearest metric size may be loose or too tight on an AWG conductor. Use a terminal rated for the size you actually have.
| AWG or kcmil | Area | Nearest standard metric size |
|---|---|---|
| 22 AWG | 0.326 mm² | 0.34 mm² |
| 20 AWG | 0.518 mm² | 0.5 mm² |
| 18 AWG | 0.823 mm² | 0.75 mm² |
| 16 AWG | 1.31 mm² | 1.5 mm² |
| 14 AWG | 2.08 mm² | 2.5 mm² |
| 12 AWG | 3.31 mm² | 4 mm² |
| 10 AWG | 5.26 mm² | 6 mm² |
| 8 AWG | 8.37 mm² | 10 mm² |
| 6 AWG | 13.3 mm² | 16 mm² |
| 4 AWG | 21.2 mm² | 25 mm² |
| 2 AWG | 33.6 mm² | 35 mm² |
| 1/0 AWG | 53.5 mm² | 50 mm² |
| 2/0 AWG | 67.4 mm² | 70 mm² |
| 4/0 AWG | 107 mm² | 95 mm² |
| 250 kcmil | 127 mm² | 120 mm² |
| 500 kcmil | 253 mm² | 240 mm² |
Conductor class matters
Lugs are designed for a stranding class. Solid and standard stranded conductors (classes 1 and 2) are smaller across than flexible ones (classes 5 and 6) of the same mm². Fine flexible cable may need a lug or die made for it.
Areas are calculated
The mm² values for AWG are worked out from the gauge diameter and rounded. Nearest-size suggestions are a guide only: always check the terminal or lug rating.
Solid, stranded or flexible. Pick the end to suit.
IEC 60228 groups conductors into classes: class 1 is solid, class 2 is stranded, class 5 is flexible and class 6 is highly flexible. The termination has to suit the class, not just the size. “Check maker” means some products are rated for it and some are not.
| Termination | Class 1 solid | Class 2 stranded | Class 5 flexible | Class 6 highly flexible |
|---|---|---|---|---|
| Bootlace ferrule | No | Check maker | Yes | Yes |
| Pre-insulated terminal | Check maker | Yes | Yes | Yes |
| DIN 46235 compression lug | Check maker | Yes | Yes | Yes |
| Standard tube lug | Check maker | Yes | Check maker | Check maker |
| Bell-mouth lug | Check maker | Yes | Yes | Yes |
| Bare wire in a screw terminal | Yes | Yes | Check maker | Check maker |
Ferrules are for strands
A ferrule on a solid conductor adds nothing and can loosen. Use ferrules on flexible conductors, and on stranded ones where the terminal maker allows. Pick a ferrule length that suits the terminal’s clamping depth.
Fine strands, bigger lugs
Flexible cable has more air between its strands, so it can be wider than a solid or stranded conductor of the same mm². Use bell-mouth lugs or lugs and dies the maker rates for flexible cable.
Sources (3) Corroborated
- SELECT: Amendment 4:2026, what’s new (opens in a new tab)BS 7671:2018+A4:2026 published 15 April 2026; previous version withdrawn 15 October 2026. Note added to 526.9.1, new Table 52.4 of conductor classes, and 526.2 now requires the conductor class to be considered.
- Thorne & Derrick: hexagonal and indent crimping (opens in a new tab)Hexagonal and indent crimp methods for lugs; DIN 46235 lugs for conductor classes 1, 2, 5 and 6; standard tube lugs for class 2.
- IET Wiring Matters: will any old terminal block do? (opens in a new tab)BS 7671 Regulation group 526; 526.9 on fine-wire conductor ends; soldered (tinned) ends not permitted in screw terminals because the solder cold-flows.
Metals. Match the lug to the conductor.
Copper and aluminium behave differently under pressure and in damp air. The lug must suit the conductor metal.
Copper lugs
Made from electrolytic copper to EN 13600 and usually tin-plated against corrosion. For copper conductors only.
Aluminium lugs
Aluminium barrels with tube sizes to DIN 46329, filled with contact compound and sealed. Barrier types stop oil escaping from paper-insulated cable. Not made for fine-stranded aluminium.
Copper-aluminium lugs
An aluminium barrel joined to a copper palm. Use them to land aluminium cable on a copper busbar or stud without corroding the joint.
Never mix
Do not crimp aluminium conductors in copper lugs, or use copper dies and codes on aluminium lugs. Use the maker’s dies for the metal.
Sources (4) Corroborated
- Thorne & Derrick: DIN 46235 lug marking (opens in a new tab)Marking example KL 22 12-150: maker, die code, M12 bolt, 150 mm².
- Klauke: pressing aluminium cable lugs (opens in a new tab)Aluminium lugs with DIN 46329 tube dimensions; barrier type; not for fine-stranded Al conductors.
- Thorne & Derrick: aluminium lugs and connectors (opens in a new tab)Use only aluminium compression lugs on aluminium conductors; marking and compound.
- Thorne & Derrick: crimping copper and aluminium (opens in a new tab)Al/Cu lugs to join aluminium conductors to copper busbars; contact compound.
Tools and dies. The crimp is only as good as the tool.
Each kind of terminal has its own crimp shape. Using the wrong tool is a common cause of loose or overheating joints.
Ferrule crimps
Ferrule tools make a square, trapezoid, hexagonal or four-indent crimp. Use the tool sold for the ferrule size, and do not crimp ferrules with insulated-terminal dies.
Insulated-terminal dies
These have nests marked red, blue and yellow, and crimp the barrel without splitting the sleeve. A full-cycle ratchet will not open until the crimp is complete, except by its release lever.
Bare-terminal dies
Uninsulated terminals use a different die profile, often an indent on the barrel. Do not use them on insulated terminals.
Lugs: hexagonal or indent
Larger lugs are crimped with a hexagonal die that squeezes the barrel evenly, or an indent die that presses a dimple into it. Use the profile, die and number of crimps the lug maker gives.
Check the tool
Ratchet tools wear and can go out of adjustment. Check them as the maker advises, and replace worn dies.
Sources (4) Corroborated
- IEC 60352-2:2024 (Genorma) (opens in a new tab)Crimped connections for stranded wire 0.05 to 10 mm² and solid wire 0.25 to 3.6 mm diameter in electrical and electronic equipment.
- Legrand Starfix ferrule tools data sheet (opens in a new tab)Ferrule tools making a four-point (four-indent) crimp; NF C 63-023 colours.
- Thorne & Derrick: hexagonal and indent crimping (opens in a new tab)Hexagonal and indent crimp methods for lugs; DIN 46235 lugs for conductor classes 1, 2, 5 and 6; standard tube lugs for class 2.
- Thorne & Derrick: DIN 48083 hexagonal dies (opens in a new tab)DIN 46235 lugs are crimped with hexagonal dies to DIN 48083 Part 4.
Shapes. Choose the right end.
The same colour code covers many shapes. Pick the shape for the terminal you are connecting to.
Ring
Closed eye over a stud or screw. Cannot slip off if the nut loosens, so it is the safe default for bolted connections.
Fork or spade
Open-ended. Fits under a screw without taking it out. Flanged forks resist slipping; plain forks are easier to dislodge.
Pin
Straight pin for clamp-type terminal blocks. On flexible cable a ferrule is usually the better choice.
Blade and receptacle
Push-on flat connectors. Tab widths such as 2.8, 4.8 and 6.3 mm follow IEC 61210. Check the receptacle matches the tab.
Butt splice
Joins two conductors end to end. Heat-shrink versions seal out moisture for vehicles, marine and outdoor use.
Bootlace ferrule
Gathers fine strands into a solid pin for screw or spring terminals. Crimped with a ferrule tool, often square or trapezoid.
Tube lug
Seamless copper or aluminium tube with a flattened palm for larger cables. Crimped with a hexagonal or indent die.
Bell-mouth lug
A tube lug with a flared entry so fine flexible strands go in without splaying.
Two-hole lug
Two bolts stop the lug turning. North American pads use NEMA spacing.
Sources (3) Corroborated
- IEC 60352-2:2024 (Genorma) (opens in a new tab)Crimped connections for stranded wire 0.05 to 10 mm² and solid wire 0.25 to 3.6 mm diameter in electrical and electronic equipment.
- ABB Spec-Kon cable termination solutions (opens in a new tab)AS/NZS 4325-1 and IEC 61238 conformant lugs; bell-mouth lugs for flexible cable.
- BURNDY NEMA-spaced board lugs (opens in a new tab)NEMA standard spacing: 1/2 in stud holes spaced 1-3/4 in apart.
In the UK. What BS 7671 asks.
BS 7671 does not list terminal colours, but it sets rules every termination must meet. The current version is BS 7671:2018+A4:2026 (the Orange Book), published 15 April 2026; the previous version, BS 7671:2018+A2:2022+A3:2024, was withdrawn on 15 October 2026.
Proper construction
Regulation 134.1.4: every joint and connection must be of proper construction for conductance, insulation, mechanical strength and protection.
Electrical connections
Regulation group 526 covers connections. Choose terminals that suit the conductor material, size, number of conductors and shape, and follow the maker’s instructions. Since A4:2026, Regulation 526.2 also requires the conductor class to be taken into account.
Fine-wire conductor ends
Regulation 526.9.1 (unchanged in A4:2026, which adds a note and Table 52.4 on conductor classes) requires that, to stop the strands of multi-wire, fine-wire and very fine-wire conductors spreading, suitable terminals are used or the conductor ends are suitably treated, for example with a ferrule. Soldering (tinning) the whole end of a stranded or fine-wire conductor is not allowed where screw terminals are used, because the solder can creep and the joint loosen.
Torque
Tighten screw terminals and bolted lugs to the torque the equipment maker gives, using a torque screwdriver or wrench. Loose terminals are a common cause of overheating.
Sources (4) Corroborated
- SELECT: Amendment 4:2026, what’s new (opens in a new tab)BS 7671:2018+A4:2026 published 15 April 2026; previous version withdrawn 15 October 2026. Note added to 526.9.1, new Table 52.4 of conductor classes, and 526.2 now requires the conductor class to be considered.
- IET: Amendment 4 (2026) to BS 7671:2018 published (opens in a new tab)BS 7671:2018+A4:2026 published 15 April 2026; the previous version withdrawn six months later.
- Voltimum: termination of conductors (opens in a new tab)BS 7671 Regulation 134.1.4: every joint and connection of proper construction for conductance, insulation, mechanical strength and protection.
- IET Wiring Matters: will any old terminal block do? (opens in a new tab)BS 7671 Regulation group 526; 526.9 on fine-wire conductor ends; soldered (tinned) ends not permitted in screw terminals because the solder cold-flows.
Before you crimp. Every time.
Colours and codes tell you what should fit. These checks make sure the joint is safe.
1Prove it dead first
Isolate, lock off and prove dead before you cut or terminate anything. Follow your safe isolation procedure.
2Match conductor, terminal and die
Check the conductor size and class, the terminal or lug rating, and the die colour or code. All three must agree.
3Strip to the right length
Strands should reach the end of the barrel or inspection hole with no insulation inside the crimp and no stray strands outside.
4Use the proper tool
Use a ratchet or hydraulic tool and the die made for that terminal. Do not crimp with pliers or a hammer.
5Inspect and tug
Check the die number on the barrel, the crimp position and the insulation. Give every crimp a firm pull: a terminal that moves must be cut off and redone.
6Never tin, never reuse
Do not solder-tin stranded ends that go into a crimp or screw terminal. Never re-crimp a terminal or reuse one that has been cut off: fit a new one.
7Aluminium needs extra care
Wire-brush the conductor, use the lug maker’s contact compound, and recheck bolted joints as the maker advises.
8Finish the joint
Fit heat-shrink or boots where needed, and torque bolted lugs to the equipment maker’s value.
This is a summary, not a substitute for training, the terminal and tool maker’s instructions or your national wiring rules.
Sources (4) Corroborated
- IEC 61238-1-1:2018 (IEC webstore) (opens in a new tab)Type tests for compression and mechanical connectors on power cables up to 1 kV.
- IEC 61238-1-3:2018 (IEC webstore) (opens in a new tab)Above 1 kV to 30 kV; copper 2.5 to 1200 mm², aluminium 16 to 1200 mm²; with parts 1-1 and 1-2 replaces IEC 61238-1:2003.
- IEC 60352-2:2024 (Genorma) (opens in a new tab)Crimped connections for stranded wire 0.05 to 10 mm² and solid wire 0.25 to 3.6 mm diameter in electrical and electronic equipment.
- Thorne & Derrick: DIN 48083 hexagonal dies (opens in a new tab)DIN 46235 lugs are crimped with hexagonal dies to DIN 48083 Part 4.
Size the cable. Then terminate it.
Work out conductor area, current density and more with the Tradefox electrical calculators.